Forum

Measure, Analyze, Control ... ask, answer, suggest.

0
Answered

D105 does not work relay via mqtt

Станислав 5 years ago in Equipment updated by Support Manager 5 years ago 5

The meter connected, MQTT data transmits, Relay subscription is enabled, ON | OFF control phrases.

I am sending from open hub:

1761607885.SETOUT = ON

and nothing

I see the topic itself in another listener - that is, it definitely comes to the broker. I tried different control phrases.

Is there any secret?)

Answer
Станислав 5 years ago

разобрались - консьюмер счетчика слушает только 15 секунд из 60, поэтому что-бы всегда работало переключение (пусть и с задержкой) - нужно слать с retained флагом. В случае с опенхабом:

Found out - the meter consumer listens for only 15 seconds out of 60, so that switching relay would always work (albeit with a delay) - you need to send it with the Retained flag. In the case of open hub:
Type switch : switch "OUT" [ 
        stateTopic="1761607885.OUT",
        commandTopic="1761607885.SETOUT",
        retained=true,
        on="ON",
        off="OFF"                   
      ]

0
Answered

D101 lite

Albert 5 years ago in Equipment updated 5 years ago 5

Хотелось бы иметь модуль типа D101, но только для контроля напряжения. А может можно добавить измерение напряжения в D105? 

Иногда надо проконтролировать напряжение, его уровень, в течении периода, например сутки. А также его пропадание, сколько раз и на как долго не было электричества.... 

0
Completed

Updates for three-phase devices D103

Support Manager 7 years ago in Equipment updated 5 years ago 5

In the comments under this post will appear information about updates for three-phase type energy monitors D103.

Enjoy measurements!

+1
Completed

Firmware Updates for smart-MAC D105

Support Manager 6 years ago in Equipment updated 5 years ago 1

FW Update 0.27 int 9 27/02/2019