0
Answered

Pulse filter settings

RAM Srl 2 weeks ago in General questions updated 1 week ago 2

Hello, I have a digital kwh meter with S0 pulse output. The datasheet of the device indicates that the pulse length is 90ms. Can the pulse filters be set as follows?
At the start [ms]:0
At the end [ms]:90

Otherwise, what do you recommend?

GOOD, I'M SATISFIED
Satisfaction mark by RAM Srl 2 weeks ago
Answered

For an electronic pulse source, set the filter to 5 ms for start and for the end, and everything will be ok.

At the start [ms]:5
At the end [ms]:5